DOS, fill in the missing links. (Read 6123 times)
Ci-aran
GDPR opt-out









DOS, fill in the missing links.
Feb 8th, 2012, 1:18pm
 
few stupid questions for the person who knows, got a bunch of pics which should make it more obvious.

http://www.flickr.com/photos/76144029@N02/?saved=1

Motor is 415v 11amp - model MPU15200U
I have a suitable DOS and overload

Q1. not sure if I need an inverter to convert from 240v to 415v?
Q2. L + N supply attached so thats easy but there is an earth screw on the Dos case and I don't know from where the earth will come from? supply cable? but its beside the T3?
Q3. T1 T2 T3 to U1 V1 W1? I figure it doesnt mater which but just thought i would double check before extinguishing my eyebrows.
Q4. on the motor what the heck are those wee blue cables up to?

Seriously appreciate any help, Thanks


Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: DOS, fill in the missing links.
Reply #1 - Feb 8th, 2012, 5:42pm
 
Q1 - Do you have a three phase (415v) supply?  If not, you do need an inverter (or variable speed drive).  This would usually go in place of your DOL (direct on line) starter.  The cost of these in inhibitive - it is cheaper to get a single phase motor.

Q2 - The earth would be from the supply and looping onto the motor.

Q3 - The three copper links link the three motor windings correctly, presenting you with the three phases, the links are in place configured in DELTA, if you moved the links to link the U2 V2 W2 together, you would be connected in star.  T1 T2 T3 would then indeed goto U1 U2 U3.  Reversing any two would reverse the direction of the motor.  You need to look at the rating plate of the motor - it will give you two different voltage ratings for star and delta.

Q4 - The two blues are for thermal protection and would be wired in series with the STOP button of the DOL stater/inverter.   Motor overheats, contactor removes power.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Ci-aran
Re: DOS, fill in the missing links.
Reply #2 - Feb 11th, 2012, 9:14am
 
Thanks for the answers but i am still a bit confused by a couple of things.

Any advice on buying an inverter for under £500?

Looping onto the motor, so that from power supply there is a earth cable to the earth screw and then another coming from the earth screw to the motor? where is the earth terminal on the motor?

U3?

can you tell me where on the the DOS the two blues should be connected?

Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: DOS, fill in the missing links.
Reply #3 - Feb 11th, 2012, 11:38am
 
Looping the earths is exactly as you describe.  The earth terminal in the motor is shown below:

Image 135   

Inverters are expensive, shopping around online is your best bet.

U3??  Not sure where you see that?

The thermal cutout blues would go in series with the red stop button, so essentially disconnect the cable from L3 at the top of the DOL Starter (which goes to the push buttons) and reconnect it via the blue cables.

Difficult to advise further to be honest.

Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 