Earthing? (Read 7078 times)
Lectrician
Administrator
Trade Member
Author
Offline
Ask The Trades
Posts: 8815
Total Thanks: 109
For This Post: 0
Braunton, North Devon
United Kingdom
Gender:
Trade: Electrician
Earthing?
May 3
rd
, 2012, 7:11pm
Extending a ring final circuit in a butchery and noticed a slight issue that would have been present from the day the site opened!
Going by the flex entry into the back box I would say the scales installers are to blame for this one!
Back to top
Need to post a picture? Click
HERE
for info!
IP Logged
The_Trician
Trade Member
Offline
Posts: 7721
Total Thanks: 8
For This Post: 0
Gender:
Trade: Electrician
Re: Earthing?
Reply #1 -
May 4
th
, 2012, 1:39pm
I take it you mean the lack of cpc connection to the front plate?
Or is it because the enclosure is all plastic?
Can't tell if it's painted steel or not from the pic.
Back to top
«
Last Edit: May 4
th
, 2012, 1:40pm by The_Trician
»
Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
IP Logged
Lectrician
Administrator
Trade Member
Author
Offline
Ask The Trades
Posts: 8815
Total Thanks: 109
For This Post: 0
Braunton, North Devon
United Kingdom
Gender:
Trade: Electrician
Re: Earthing?
Reply #2 -
May 4
th
, 2012, 4:37pm
It's a typical MK masterseal moulded plastic enclosure. The two earth terminals are NOT linked! One is marked as EARTH the other as LOOP, in reality you use either for the earth, but not quite like that!
Back to top
Need to post a picture? Click
HERE
for info!
IP Logged
scotspark
Trade Member
Offline
mmmmm it's gonna cost
you!!
Posts: 3074
Total Thanks: 10
For This Post: 0
scotland
Scotland
Gender:
Trade: Electrician
Re: Earthing?
Reply #3 -
May 6
th
, 2012, 1:13pm
seen that before
had a spark from another firm giving us a hand on a job and he fitted 6 MK masterseal twin sockets with 1 earth into socket frontplate and one into backbox with no link!!!!
never had him again
Back to top
brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
IP Logged
Lectrician
Administrator
Trade Member
Author
Offline
Ask The Trades
Posts: 8815
Total Thanks: 109
For This Post: 0
Braunton, North Devon
United Kingdom
Gender:
Trade: Electrician
Re: Earthing?
Reply #4 -
May 6
th
, 2012, 3:02pm
I can remember taking a surface moulded socket apart looking for a fault and noticed an earth flylead from the socket to the back box screw of the plastic box! Each socket I came to had one.
It was an install done by a maintenance guy in a small independant school, all MMT2 trunking drops from ceiling down to new sockets for the interactive whiteboards.
Back to top
Need to post a picture? Click
HERE
for info!
IP Logged
LSpark
Global Moderator
Trade Member
Author
Offline
Posts: 8069
Total Thanks: 3
For This Post: 0
London, UK
United Kingdom
Gender:
Trade: Electrician
Re: Earthing?
Reply #5 -
May 7
th
, 2012, 1:10pm
It's amazing the lack of thought shown isn't it, perhaps this is a good example of why inspection & testing is so important!
Or perhaps it's just to many of the wrong people doing the job!
Back to top
IP Logged
The_Trician
Trade Member
Offline
Posts: 7721
Total Thanks: 8
For This Post: 0
Gender:
Trade: Electrician
Re: Earthing?
Reply #6 -
May 7
th
, 2012, 10:16pm
I had 3 metalclad 20A DP switches last week where there was no flying lead to the front switch plate, nor any banjos fitted to the SWA glands - Done by a NIC Approved Contractor too.
Despite the cable being a 3 core with 1 x core used as a cpc too!
Back to top
Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
IP Logged
Pages: 1
(Moderator: Lectrician) - (Moderator Group: Board Moderator)
<
Previous Topic
|
Next Topic
>
Ask The Trades
›
DIY Forum
›
Electrical Questions
› Earthing?
Forum Jump »
Home
» 10 most recent Posts
» 10 most recent Topics
DIY Forum
- Electrical Questions ««
- Plumbing Questions
- Carpentry Questions
- Building Questions
- Painting, Decorating & Tiling Questions
- Alarms, Phones, Aerials, CCTV & Datacomms
Public Forum
- Just Talk
- Humour
- The Forum
- Trade Applications
Ask The Trades
» Powered by
YaBB 2.3
!
YaBB
© 2000-2008. All Rights Reserved.