Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
May 18th, 2024, 7:51pm
Quote: One step beyond.....


Page Index Toggle Pages: 1
Send Topic Print
Conduit for ground floor circuit drops (Read 1629 times)
Gary
GDPR opt-out









Conduit for ground floor circuit drops
Jan 19th, 2013, 10:58pm
 
This seems to be hotly debated subject on the various forums.

Doing first fix on rewire. Solid ground floor so ground floor circuits run in the ceiling and drop down the walls to the circuits/light switches etc.

The existing outlets were done in the 60's and the drops appear to be in 20mm equivalent (imperial) round steel conduit with two cables in each (for ring sockets) although I haven't measured it yet.

Is it still permissible to use 20mm conduit with two 2.5mm cables in, given grouping factors etc. It is only for the couple of metres where the circuit drops from the ceiling.

The remainder of the circuit will be clipped to the joists in the ceiling void.

Plan was to use a single 20mm or 25mm round conduit for each socket drop (Using 35mm boxes with dual knockouts)

There is also a couple of sockets where the conduit will be in an insulated stud wall - again only for the drop from the ceiling.

Thanks
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Conduit for ground floor circuit drops
Reply #1 - Jan 20th, 2013, 9:21pm
 
Nothing wrong with T+E in conduit, or sharing conduit.  If you bunched several circuits you would need to down-rate, but a single circuit for a socket is fine.

2 x 2.5mm² will just squeeze down a 20mm conduit if you keep the cables flat.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print