Running 2 x 3 gang sockets off a consumer unit (Read 3429 times)
morgaf02
GDPR opt-out
Running 2 x 3 gang sockets off a consumer unit
Mar 4
th
, 2013, 9:27pm
Im normally pretty good with electrics, but need a bit of advice.
Im having some bespoke entertainment furniture installed soon and i need to rearrange the plug sockets. I was looking at running a spur off of an existing 2 gang socket but am unable to do so as the existing one is already a spur.
As the consumer unit is near (under stairs cupboard) to where i want the sockets can i run 2x 3 gang sockets straight off of the consumer unit? There are spare rcd's on the unit.
Any help is appreciated.
Thanks.
Back to top
IP Logged
Lectrician
Administrator
Trade Member
Author
Offline
Ask The Trades
Posts: 8814
Total Thanks: 109
For This Post: 0
Braunton, North Devon
United Kingdom
Gender:
Trade: Electrician
Re: Running 2 x 3 gang sockets off a consumer unit
Reply #1 -
Mar 5
th
, 2013, 6:48pm
Yes, 2.5mm² from a B20 MCB or 4mm² on a B32 MCB. These MCB's should have RCD protection.
Can you take a photo of the Consumer Unit as it is?
Back to top
Need to post a picture? Click
HERE
for info!
IP Logged
morgaf02
GDPR opt-out
Total Thanks: 109
For This Post: 0
Re: Running 2 x 3 gang sockets off a consumer unit
Reply #2 -
Mar 6
th
, 2013, 9:43am
Thanks for getting back to me. Here are a couple of pics.
Back to top
IP Logged
Lectrician
Administrator
Trade Member
Author
Offline
Ask The Trades
Posts: 8814
Total Thanks: 109
For This Post: 0
Braunton, North Devon
United Kingdom
Gender:
Trade: Electrician
Re: Running 2 x 3 gang sockets off a consumer unit
Reply #3 -
Mar 6
th
, 2013, 5:00pm
You would need to get a wylex B20 or B32 MCB and fit it to the RCD side of that board (the very far left empty way). You cannot use the B6 MCB which is empty - it is too small, and on the wrong side of the RCD.
Back to top
Need to post a picture? Click
HERE
for info!
IP Logged
morgaf02
GDPR opt-out
Total Thanks: 109
For This Post: 0
Re: Running 2 x 3 gang sockets off a consumer unit
Reply #4 -
Mar 6
th
, 2013, 8:01pm
Thank you for the help. Much appreciated.
Back to top
IP Logged
Pages: 1
(Moderator: Lectrician) - (Moderator Group: Board Moderator)
<
Previous Topic
|
Next Topic
>
Ask The Trades
›
DIY Forum
›
Electrical Questions
› Running 2 x 3 gang sockets off a consumer unit
Forum Jump »
Home
» 10 most recent Posts
» 10 most recent Topics
DIY Forum
- Electrical Questions ««
- Plumbing Questions
- Carpentry Questions
- Building Questions
- Painting, Decorating & Tiling Questions
- Alarms, Phones, Aerials, CCTV & Datacomms
Public Forum
- Just Talk
- Humour
- The Forum
- Trade Applications
Ask The Trades
» Powered by
YaBB 2.3
!
YaBB
© 2000-2008. All Rights Reserved.