No Earth...? (Read 3421 times)
owenwales
GDPR opt-out









No Earth...?
Apr 20th, 2013, 9:34am
 
Hello all, Hopefully someone will understand. Smiley

Sorry if it seems a tad garbled.


This week we had British Gas out to survey for a new boiler. They told us that there is no earth in the property. I was advised to find out if PME was available in the area, it was and they have come out to fit something to the electrical box.
British Gas said it was fine to purchase 10mm earth cable and install it but NOT to connect, bond it or split it.

At the moment I have 2 cables hanging , one is going to be coming from the mains water and the other from the gas pipe.


Do these get connected to the earth bar in the consumer box?


Also is another length of earth cable going to be connected from the earth bar into the PME connection to create earth in the property?


Sorry if its vague.


Long story short...

Conflicting advice from British gas and the PME installer, British gas said there was zero earth and suggested the pme/earth spike... the PME installer said there was earth but not a major amount.
We were basically unsure whether Bgas were using scare tactics to increase work that would be needed. We were planning on replacing the boiler with them and were quoted almost 4000 for the work including the pme/spike install.
The PME installer said that British Gas were scaremongering every one of their boilercare customers and the rise in pme installing had increased over 80%. We have been in the property over 15 yrs without any issues, we may have just been lucky so far.


Hope someone can clear a few things up as I dont want to waste money on work/electricians that may not have been required.

thanks
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: No Earth...?
Reply #1 - Apr 20th, 2013, 12:03pm
 
Perhaps the external earth fault loop was high on a TN-S system, and they converted to PME to reduce this.

Can you take a photo of the service position?

You should have a 16mm earth from the PME terminal (or the TN-S terminal) to the Main Earthing Termial (MET).  The MET can be the earth bar in the consumer unit on modern boards with room.  You should then have a 10mm earth from the consumer unit to the gas and water (two runs is preferred).  If you wanted to do a single run of 10mm, and loop past the gas or water (both on one cable), the one you loop past MUST NOT have the bonding conductor cut to terminate, just stripped and past around the terminal.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
1john
Re: No Earth...?
Reply #2 - Apr 20th, 2013, 10:38pm
 
Could just be a TT install and when BG took a Zs they did'nt understand the reading being high.
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: No Earth...?
Reply #3 - Apr 21st, 2013, 8:02am
 
Yep, or perhaps they spotted a TT with an ELCB (voltage operated) still in place.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
woodsmith
Global Moderator
Trade Member
Author
*****
Offline


Posts: 4397


Total Thanks: 135
For This Post: 0


Gender: male

Trade: Joiner

Re: No Earth...?
Reply #4 - Apr 21st, 2013, 11:19am
 
I don't know about the earthing but British Gas do not have the greatest reputation for boiler installation and I would get a couple more quotes; you should find a local heating engineer who will charge a LOT less.