memera 2000
Sep 13th, 2013, 3:51pm
 
hi need to replace a fuse in my fuse box but can't get old one out .have switched off main switch  and pulled but it will not budge . please help is there a trick to doing this.
Back to top
 
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #1 - Sep 13th, 2013, 3:55pm
 
Assuming its one of these:

...

It should pull out pretty easily.

If it has overheated, it my be "welded" shut. Do you know it's blown, or are you assuming?  Perhaps it has overheated due to a loose connection inside.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: memera 2000
Reply #2 - Sep 16th, 2013, 6:50am
 
Sorry if it's a silly question but... Have you released the DIN rail catch? The photo Lectrician posted shows two of these in the unlatch position (I think). You will probably have to remove a bus bar as well.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: memera 2000
Reply #3 - Sep 16th, 2013, 4:19pm
 
thats just a terminal screw cover CW

no need to remove any screws to change a fuse.

unless its welded and you need to change carrier that is.
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: memera 2000
Reply #4 - Sep 17th, 2013, 7:42am
 
My mistake.  I have a different CU and the MCB don't just pull out if that's what you are trying to do.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #5 - Sep 17th, 2013, 5:14pm
 
These are not MCBs, they are HRC fuse carriers.  The module is identical to an MCB in size and it fits to the dinrails in the same way. To swap a fuse, you pull the carrier out.  The assembly stays on the dinrails/busbar.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: memera 2000
Reply #6 - Oct 27th, 2013, 1:18pm
 
LEC,
Where can those MEM Fuse carriers be had from?

I have a MEMSHIELD 2 3 phase board which feeds 3 single phase consumer units in a local hotel via 40A type B mcbs. I am thinking that these do not provide proper fault discrimination with the individual consumer unit mcbs and would like to swap em out for Fuses instead.

I've looked and looked but have never found any available before.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: memera 2000
Reply #7 - Oct 27th, 2013, 2:07pm
 
quick google

http://www.ebay.co.uk/bhp/memera-fuses

http://www.ebay.co.uk/sch/i.html?_kw=memera+2000+hrc+fuse+mem

http://www.ebay.co.uk/bhp/mem-memera

http://www.ebay.co.uk/bhp/mem-fuse-carrier


don't know if they are suitable for 3 phase boards.

the commercial mcb's fitted in domestic boards but the domestic mcb's didn't fit in the commercial boards.

Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #8 - Oct 27th, 2013, 3:12pm
 
They are no longer available from new.  The 45amp ones take up two ways.  They would fit the TP boards (it was the newer AD MCB's that would not bit the commercial boards due to narrower busbars/terminals on the newer AD models).

A C type MCB is always preferable on sub-mains.  What size cable is it?  Could you go up from a 40?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #9 - Oct 27th, 2013, 3:14pm
 
scotspark wrote on Oct 27th, 2013, 2:07pm:
quick google

http://www.ebay.co.uk/bhp/memera-fuses

http://www.ebay.co.uk/sch/i.html?_kw=memera+2000+hrc+fuse+mem

http://www.ebay.co.uk/bhp/mem-memera

http://www.ebay.co.uk/bhp/mem-fuse-carrier


don't know if they are suitable for 3 phase boards.

the commercial mcb's fitted in domestic boards but the domestic mcb's didn't fit in the commercial boards.



Only the second link there would be any good  Wink

This is the larger ones:
...

This is the normal din sized:
...
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: memera 2000
Reply #10 - Oct 27th, 2013, 9:11pm
 
The submains from the 3 ph board are run in what in looks like 16mm T&E so am thinking around 50A max. Might get away with 63a but without checking I can't say for certain.
Am thinking Zdb + Zs at C/U subccts might be exceeded if we go any higher.
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: memera 2000
Reply #11 - Oct 28th, 2013, 6:30pm
 
why would sub ccts be affected by the submains mcb/fuse?
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #12 - Oct 28th, 2013, 6:53pm
 
Poor discrimination on magnetic (not thermal) trip side.  Get a short on the sockets, and you could trip the submain, not the final circuit.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: memera 2000
Reply #13 - Oct 29th, 2013, 8:36pm
 
Yes I understand tha lec

The_Trician wrote on Oct 27th, 2013, 9:11pm:
The submains from the 3 ph board are run in what in looks like 16mm T&E so am thinking around 50A max. Might get away with 63a but without checking I can't say for certain.
Am thinking Zdb + Zs at C/U subccts might be exceeded if we go any higher.



Its this part I didnt get?

The sub cct either complies or it doesnt?

upgrading the supply fuse to the board makes no difference.
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: memera 2000
Reply #14 - Oct 29th, 2013, 9:18pm
 
See what you mean.

The Zdb at the sub board would have to meet the max Zs for the C type or HRC fuse being fitted to protect the submain, but the final circuits from the submain would not be affected, they have their own overcurrent devices, and their own max Zs figures.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
scotspark
Trade Member
*****
Offline

mmmmm it's gonna cost
you!!
Posts: 3074


Total Thanks: 10
For This Post: 0


scotland, Scotland
scotland
Scotland

Gender: male

Trade: Electrician



Re: memera 2000
Reply #15 - Oct 30th, 2013, 10:16pm
 
Exactly.

TT only needs to worry about the sub main cct he is upgrading the fuse/mcb on
Back to top
 

brown to red and blue to f****&&&&ommited!!!!!!!!!!!!!!!!!!!!!!!!!!!
Thank User For This Post View members image gallery  
IP Logged
 