Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
Apr 27th, 2024, 5:27pm
Quote: A conscience is what hurts when all your other parts feel so good.


Page Index Toggle Pages: 1
Send Topic Print
Running Cables in walls (Read 11181 times)
DoWellSon
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 14


Total Thanks: 0
For This Post: 0



Running Cables in walls
Sep 28th, 2004, 10:08pm
 
Reading the OSG Sec 7 pg 53, regarding permitted cable routes. I'm a little unsure of the intent of running horizontally.
Can you run cable horizontally between two sockets? The wording seems to indicate that the only time you need metal conduit is for diagonally and less than 50mm below surface. I ask as  haven't seen it run horizontally between sockets and was under the impression it was a no no. Any thoughts?
Back to top
 
Thank User For This Post  
IP Logged
 
JerryD
Re: Running Cables in walls
Reply #1 - Sep 28th, 2004, 10:53pm
 
I was also under the impression that this was a no no but the OSG clearly says this is ok.  You must run horizontally or vertically from the faceplate.

Diagonally is still a no no unless it is deeper than 50mm or is enclosed in earthed metal trunking or conduit.

So a 100mm thick partition wall is not suitable for the 50mm deep rule as far as I can see.

Back to top
« Last Edit: Sep 28th, 2004, 10:54pm by JerryD »  
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Running Cables in walls
Reply #2 - Sep 29th, 2004, 1:33am
 
horrizontally from an accesory is a permitted route by regs but most sparkys consider it bad practice nonetheless

kinda like running a shower cuircuit with no rcd the regs allow it but that doesn't mean most sparkys think it is a good idea
Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
DoWellSon
Junior Member
**
Offline

I love YaBB 1G - SP1!

Posts: 14


Total Thanks: 0
For This Post: 0



Re: Running Cables in walls
Reply #3 - Sep 29th, 2004, 8:51am
 
Thanks  - just wanted clarification. I read it that you could but agree it appears to be bad practice.
Back to top
 
Thank User For This Post  
IP Logged
 
fubar
Junior Member
**
Offline


Posts: 10


Total Thanks: 0
For This Post: 0


Gender: male

Re: Running Cables in walls
Reply #4 - Sep 30th, 2004, 2:43pm
 
[quote author=plugwash  link=1096405718/0#2 date=1096418019]horrizontally from an accesory is a permitted route by regs but most sparkys consider it bad practice nonetheless
[/quote]

Partly because it encourages people who don't know better to run horizontally into the corner and then along the adjacent wall.  Very bad as the 90 degree change of direction would have a tiny bend radius that would be well outside the permitted bend radius and could cause heating of the cable or even break the conductors - either of which coud cause a fire.

And partly because a deep channel could seriously weaken the structural integrity of a solid wall.
Back to top
 

Michael&&
Thank User For This Post  
IP Logged
 
sparkyjonny
Re: Running Cables in walls
Reply #5 - Oct 17th, 2004, 7:42pm
 
Hi everyone - just moved over from Screwfix -  fed up of it being down all the time!
Does anyone know what NICEICs recommendations for running under a bay window or in a dwarf wall on a conservatory is?  I know horizontal runs would be acceptable if there is an accessory mounted on each angle of the wall, but what about if a customer wants a socket on a section of dwarf wall without any on the adjacent sections? - i'm thinking of the common rectangular conservatory with half a hexagon on the end.  Is it just a case of either underground or earthed capping?  Or is the top of the dwarf wall or bottom section of wall beneath a bay window classable a standard wall, so cables can be routed all the way around within the top 150mm?
Cheers guys.
Back to top
 
Thank User For This Post  
IP Logged
 
JerryD
Re: Running Cables in walls
Reply #6 - Oct 17th, 2004, 7:48pm
 
The permitted zone is 150mm down from the ceiling, so you can't run it horizontally in the dwarf wall as you suggest.  Run it under the floor or in an earthed conduit.

I know the regs say 'within 150m from the top of the wall' but from the osg picture it looks like they mean from the ceiling.
Back to top
« Last Edit: Oct 17th, 2004, 7:51pm by JerryD »  
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #7 - Oct 17th, 2004, 9:17pm
 
That good old question - we use SWA in concervatories under the floor screed.  Use 35mm deep boxes in the wall, and terminate the swa via conduit couplers and serrated washers/bushes into the galv back box.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
sparkyjonny
Re: Running Cables in walls
Reply #8 - Oct 18th, 2004, 9:38am
 
Like that idea Lectrician.  I assume SWA could also be run horizontally, as the earthed armour gives it the same level of protection (if not more) than that offered by earthed steel capping?  May need a channel chasing into the brickwork though...
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #9 - Oct 18th, 2004, 12:08pm
 
SWA provides 'mechanical protection' same as steel capping does
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Running Cables in walls
Reply #10 - Oct 18th, 2004, 1:36pm
 
if you want something thinner than SWA which can be chased in directly out of zones you could consider MICC

from what i c an gather the stuff is trikier to work with and pricier than SWA though
Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
sparkyjonny
Re: Running Cables in walls
Reply #11 - Oct 18th, 2004, 4:53pm
 
Yeah - the size is tempting, but heard that its a nightmare to terminate unless you're experienced.  Anyone had experience of pyro?
Back to top
 
Thank User For This Post  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #12 - Oct 18th, 2004, 5:03pm
 
yup, never ever try and rush the making off process Roll Eyes
and make sure ya test it after terminating- would be a bitch to find it fails after its all plastered up  Wink

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #13 - Oct 18th, 2004, 5:07pm
 
Unless you have done it before, don't  Wink

SWA much quicker, works out cheaper too, 3-core, so armour is not sole earth, and then doesnt matter if the gland is not the best.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #14 - Oct 18th, 2004, 6:21pm
 

SWA much quicker, works out cheaper too, 3-core, so armour is not sole earth, and then doesnt matter if the gland is not the best. [/quote]

Armour must be earthed properly L/S, otherwise it could remain LIVE under fault conditions, regardless of whether an integral core is used as the cpc instead.

No good earthing via an extra cable core if there is a risk that the armouring could become live without being detected, so gland termination should be done properly regardless mate.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Running Cables in walls
Reply #15 - Oct 18th, 2004, 8:37pm
 
You know what I meant, if it's done with a copper core, then it would effectively have double earthing, because both earths would have to be connected together.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print