SWA much quicker, works out cheaper too, 3-core, so armour is not sole earth, and then doesnt matter if the gland is not the best. [/quote]
Armour must be earthed properly L/S, otherwise it could remain LIVE under fault conditions, regardless of whether an integral core is used as the cpc instead.
No good earthing via an extra cable core if there is a risk that the armouring could become live without being detected, so gland termination should be done properly regardless mate.