[quote author=Adama link=1098040520/0#0 date=1098040520] Originally when we made up the plan, I told him my existing consumer unit was full, so he told me I would either have to replace it with a new split board or alternatively, buy a small RCD protected CU and wire that into my main CU, then wire up to my shed from that second CU. [/quote]
I'm not sure he did tell you that - why would he tell you to wire a second CU in to your main CU as a way round the fact that your main CU was full? Where would you connect it?
Quote:Now it transpires that I do actually have a spare way on my CU (which is not a split board). So, here's my plan.
Does it have any RCD protection?
Quote:The donated cable I can't really identify a size (because I'm too thick to work it out...) it's AEI BS5467 600/1000V 4-core cable with an overall diameter of 20mm
The 4-core SWA that TLC sell:
6mm²: 18.3mm O.D.
10mm²: 20.3mm O.D.
Quote:- each core has a diameter of about 4mm,
4mm dia = 2mm radius, therefore 12.58mm²
Quote:but each core is made up of 7 copper wires, each with a diameter of about 1mm - so would this be 6mm cable?
1mm dia = 0.5mm radius, therefore 0.785mm² x 7 = 5.49mm²
What are you using to measure the various diameters you have quoted?
Quote:From the weatherproof switch to the position of the water feature / lights is about 15m and I will be utilising the 4-core armoured cable again for this run, terminating in some sort of junction box (not decided yet - any advice?).
You will struggle to terminate SWA inside the box of the Masterseal switch, so you'll need to have a suitable adaptable box at both ends.
Quote:I'm hoping to utilise the two live wires separately for the two systems and sharing the neutral and earth. (i.e. L1 supplies to the fountain, L2 supplies to the 4 spot lights, N and E common) so that I can switch the lights and the fountain separately through the one cable run. Am I okay to do this?!?
I don't see anything wrong with this - it is not a "borrowed neutral" and I'm not sure what TT is concerned about - it's just the same as a normal lighting circuit - one original live feed, many switched lives and one neutral.
Quote:Finally, the fourth radial circuit would purely provide a double socket, 1 will be used by a tumble dryer (which says on it 250W - 2900W MAX) and the other socket will be used for either a lawnmower 1.15kW or a strimmer 250W with potentially both sockets being used at the same time.
NO - you cannot do this - a double socket is rated at 13A, not 26A, so if you want to use the lawnmower and the T/D at the same time, then you must buy a petrol mower or fit two sockets.
Quote:I had initially planned to use a 16A MCB for that circuit, but according to the TLC calculator, there is a potential maximum load of 17.39A so should I use a 20A MCB for this circuit instead of the 16A?
Yup - 20A breaker on a 2.5mm² radial.
Quote:All of this would be protected by a 40A 30mA RCD (correct size given the information above?) in the consumer unit in the shed.
That would be fine.
Quote:From the house to the shed I would be running about 8-10 meters of the 4-core armoured cable clipped to the wall. I am planning on attaching it directly to my existing house CU on the spare with utilising a 40A MCB
More struggles - you'd find it much easier to terminate the SWA in a box, and run 6mm² T/E into the CU.
Quote:- this is probably the part I am most unsure of - as two people have told me that I should have an RCD at the house end too
No - you do not need, and do not want, an RCD at the house end as well.
Quote:which would probably entail exchanging my existing CU with a split board (or can I get a 1 unit width RCD to go in my existing CU and supply outside without having a split board CU??).
Depending on the make of board you might be able to get a single-module RCBO, but as I said, you really don't need an RCD at the house end.
However, you might like to consider replacing the CU with a split-load one anyway - do you never use any of the ground floor sockets to supply equipment outdoors?
Quote:Two other people have told me that I don't need an RCD at the house end. This would be my preferred method, just an MCB protected circuit heading outside via the armoured cable to the shed CU which has the RCD protection. If someone could clearly lay out my options and the preferred solution to this part of the plan I would be very grateful.
40A MCB - 6mm² T/E to metal box - SWA to metal box - 6mm T/E to shed CU.
Quote:Oh, I am also (on advice) considering that the armoured cable from the house to the shed stops just outside the shed at an industrial socket (such as
http://www.tlc-direct.co.uk/Products/GW240slash63slash3S.html) then having a fly lead from that into the shed CU which would be about 2 meters cable - but I'm not sure what cable I would need to build this fly lead from - can't really find any flex that is heavy duty enough (can only find 4.0mm 32A flex) and twin and earth would be impractical for this... but the idea of being able to detach the shed and therefore also isolate the 4 circuits and the CU merely by removing the fly-lead has it's plus points. Any thoughts on this?
My thoughts are that if you want to be able to isolate the shed (I'm sure you have your reasons), and you want to do it frequently enough not to use the MCB at the house, then you should supply the shed via a switch-fuse in the house, and isolate from there.