Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
Apr 28th, 2024, 11:19am
Quote: If a tree falls in the forest and no one is around to see it, do the other trees make fun of it?


Pages: 1 
Send Topic Print
240 Volt Generator (Read 11698 times)
engineer1958
GDPR opt-out









240 Volt Generator
Oct 19th, 2004, 11:16pm
 
Will a standard RCD socket / adaptor provide protection if wired into a site generator?
Back to top
 
 
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #1 - Oct 19th, 2004, 11:22pm
 
yup they work on inbalence

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
chtechie
Re: 240 Volt Generator
Reply #2 - Oct 19th, 2004, 11:56pm
 
Ooh Err Missus are sites not required to use 110V power ?
Back to top
 
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 240 Volt Generator
Reply #3 - Oct 20th, 2004, 12:00am
 
depends on the earthing arangement of the generator

useing a multimeter mesure resistance from neutral-earth on the generators output

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #4 - Oct 20th, 2004, 7:44am
 
and the gen needs roding down to provide a path through you, the earth and up the rod to achieve an inbalance  Shocked
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 240 Volt Generator
Reply #5 - Oct 20th, 2004, 2:29pm
 
basically there are two ways the output of a generator can be wired

in this peice "earth" refers to the earth wire of the wiring which may or may not be connected to real earth

1: "earth" terminal connected to generator case neutral terminal only connected to generator coils

2: same as above but "earth" bonded to neutral

the "earth" may or may not be connected to real earth

the advantage of possibility 1 is you need TWO faults to cause any danger

the advantage of possibility 2 is that it works with rcds

possibility 2 is the only real option with 3 phase as a fault from one of the phase cores of an isolated neutral system to earth would bring the other phase cores 415V from earth OUCH!!!

the generator output "earth" may or may not be rodded down to real earth this has its own advantages and disadvantaged but with a small portable generator isn't likely to be very practical

for a generator running a single power tool option 1 is probablly the safer especilly if the power tool is double insulated as with a double insulated power tool a short to "earth" is impossible anyway and having it safe to touch either individual core in the event of a fault is a definate plus

for larger systems option 2 tends to be a better bet as the chance of an undetected fault increases and the disadvantages of having live dangerous even without other faults are outweighed by the fact that rcds and mcbs can disconnect "earth" faults in the normal way furthermore larger systems are more likely to be three phase which pretty much mandates option 2

the ultimate soloution from a safety point of view would be to use option 1 with a voltage based earth fault detection (like a hospital IT system) but this would be cost prohibitive and unlike rcds would not allow detection of where on the system an earth fault was

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 240 Volt Generator
Reply #6 - Oct 20th, 2004, 2:32pm
 
you can ofc convert a generator that is wired to option 1 to option 2 by putting a N-E link in the plug but if you do so then it is important to mark that lead with a warning label so it doesn't get used elsewhere
Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #7 - Oct 20th, 2004, 3:27pm
 
Small portable gen sets sold by builders merchants and the like are usually 'possibiltiy 1'.  
Back to top
« Last Edit: Oct 20th, 2004, 3:27pm by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 240 Volt Generator
Reply #8 - Oct 21st, 2004, 12:32am
 
moved here so i could refer to it in a post on screwfix Wink

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
HM
Super Member
*****
Offline

Chief Turd Polisher
Posts: 5072


Total Thanks: 0
For This Post: 0


Gender: male

Re: 240 Volt Generator
Reply #9 - Oct 21st, 2004, 6:49am
 
[quote author=plugwash  link=1098315135/0#5 date=1098278985]basically there are two ways the output of a generator can be wired [/quote]

Could I suggest that this article is made accessible as a downloadable fact sheet or something on this web site? Connecting up gennies is one of those subjects where the great unwashed must be as confused as anything about the possibilities.

Andrew
Back to top
 

If you aren't always sure of the right answer don't take up a career in the bomb squad
Thank User For This Post  
IP Logged
 
JerryD
Re: 240 Volt Generator
Reply #10 - Oct 21st, 2004, 8:00am
 
What are the dangers then, of connecting a generator output into a domestic supply as a temporary supply?

What we do when we get a power cut (we are very rural), is turn off the supply at the consumer unit then plug the generator output into a socket in the garage (garage is run off house supply so is connected to house).  This provides a 3kva suppy to the entire house.

We have to limit what we use, obviously, but it provides lighting and minimal use of the ring mains.

Is there anything 'dodgy' about this set up?

We have a separate supply to another consumer unit in an extension, so we leave that connected to the National Grid and switch the lights on, that way we know when the power cut is ended as all those lights come on.  We then disconnect the generator and carry on as normal.

What I'm not sure about is what protection we have regarding short circuit protection?

(our house is on a TN-C-S supply, if that is relevant)

Any advice would be appreciated as we are entering the 'power cut' season................)
Back to top
 
Thank User For This Post  
IP Logged
 
HM
Super Member
*****
Offline

Chief Turd Polisher
Posts: 5072


Total Thanks: 0
For This Post: 0


Gender: male

Re: 240 Volt Generator
Reply #11 - Oct 21st, 2004, 8:28am
 
[quote author=JerryD  link=1098315135/0#10 date=1098342057]What are the dangers then, of connecting a generator output into a domestic supply as a temporary supply? [/quote]

I can't speak for the installation from a technical perspective, but one thing that alarms me from what you are doing is that there appears to be no protection in place to stop someone re-enabling the consumer unit whilst the generator is operational.

So your generator might potentially (good pun...) be backfeeding the national grid.

Plus, if the mains comes back on your installation might get fried by two sources fighting each other (the generator is bound to lose, but at what cost?).

Andrew
Back to top
 

If you aren't always sure of the right answer don't take up a career in the bomb squad
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #12 - Oct 21st, 2004, 2:18pm
 
lol, I realllly don't like the sound of that operation  Shocked
Back to top
« Last Edit: Oct 21st, 2004, 2:19pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #13 - Oct 21st, 2004, 3:29pm
 
Seen it so many times before - two plugs on the end of a length of flex (for a start that is down right dangerous  Shocked).

The earthing arrangement would need looking into for your particular generator, and thought must be given to the fact that the earthing in a building using a TN-C-S supply will be at neutral potential even with the CU switch off.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 240 Volt Generator
Reply #14 - Oct 21st, 2004, 3:31pm
 
60 or 100amp DP changeover switches are not too expensive nowadays, one of these, with a cable to the generator would suit the situation better.  You would still need to lok into the correct type of earthing system for the generator.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 240 Volt Generator
Reply #15 - Oct 21st, 2004, 4:09pm
 
[quote author=JerryD  link=1098315135/0#10 date=1098342057]What are the dangers then, of connecting a generator output into a domestic supply as a temporary supply?

What we do when we get a power cut (we are very rural), is turn off the supply at the consumer unit then plug the generator output into a socket in the garage (garage is run off house supply so is connected to house).  This provides a 3kva suppy to the entire house.

We have to limit what we use, obviously, but it provides lighting and minimal use of the ring mains.

Is there anything 'dodgy' about this set up?

[/quote]

there are four main issues with this
the first is overload but that should be taken care of by the plug fuses

the second is the plug getting unplugged (hence you have a live plug dangleing)

the third is the possibility of someone turning the main swich in the CU back on,

and finally if the generator has an isolated neutral you should probablly bond that to earth to allow rcds to work.

how about the following
32A breaker in main CU
    |
32A supply changeover switch----generator
    |
small CU feeding lights and a few sockets (which should be made easy to identify from the normal sockets possiblly by using a different style of plate or something)

if your generator has an isolated netral then fit a link from neutral-earth in the plug used to connect to the generator

this setup also means you won't have to go round turning off all the high load appliances before switching the changeover switch

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
spongebob
Re: 240 Volt Generator
Reply #16 - Oct 21st, 2004, 10:20pm
 
Didn't really understand any of this post. I'm taking it that it refers only to running a whole house off a genny. None of the above would apply when running a single appliance from a generator, for instance a combi boiler, or would it?
Back to top
 
Thank User For This Post  
IP Logged
 
JerryD
Re: 240 Volt Generator
Reply #17 - Oct 21st, 2004, 11:54pm
 
Thanks for the replies.  

1) Overload taken care of by plug fuses

2) Getting unplugged - I agree potentially dangerous but I'm the only one ever likely to touch any of this gear and I'm well aware of the risks.  

3) Accidentally turning back on the cons. unit.  Again not likely as I am the only one ever likely to touch this.  My wife and two daughters don't even know how to reset the mcb's!!  "too technical.............."  Grin

4) If generator has isolated neutral.................. Hmmmmmm, I was keeping up with you till then  Grin  What does this mean?  Why you no speeka engrish  Embarrassed

btw, the main advantage of the genny during a power cut is to have all our outside driveway lights on, so we can look smug in front of neighbours trying to find their candles  8)
Back to top
 
Thank User For This Post  
IP Logged
 
HM
Super Member
*****
Offline

Chief Turd Polisher
Posts: 5072


Total Thanks: 0
For This Post: 0


Gender: male

Re: 240 Volt Generator
Reply #18 - Oct 22nd, 2004, 12:03am
 
[quote author=JerryD  link=1098315135/15#17 date=1098399254]2) Getting unplugged - I agree potentially dangerous but I'm the only one ever likely to touch any of this gear and I'm well aware of the risks [/quote]

To be honest that would be a major concern for me. If you fell over and conked your head or something there's every chance someone could switch the power back on without realising.

I would strongly suggest fitting an isolator switch in the circuit so that it is impossible for both genny and mains to be activated together.

Andrew
Back to top
 

If you aren't always sure of the right answer don't take up a career in the bomb squad
Thank User For This Post  
IP Logged
 
JerryD
Re: 240 Volt Generator
Reply #19 - Oct 22nd, 2004, 12:23am
 
Yup Andrew, you're right.......

Keep taking the risk until the inevitable happens  Sad

I've stuck that on my list of jobs to do


Back to top
 
Thank User For This Post  
IP Logged
 
HM
Super Member
*****
Offline

Chief Turd Polisher
Posts: 5072


Total Thanks: 0
For This Post: 0


Gender: male

Re: 240 Volt Generator
Reply #20 - Oct 22nd, 2004, 7:25am
 
[quote author=JerryD  link=1098315135/15#19 date=1098401022]I've stuck that on my list of jobs to do [/quote]

Oi! That's copyright ©! My catchphrase is "I take care of round tuits".

Andrew
Back to top
 

If you aren't always sure of the right answer don't take up a career in the bomb squad
Thank User For This Post  
IP Logged
 
squirrel
Trade Member
*****
Offline

d'oh
Posts: 801


Total Thanks: 1
For This Post: 0


Gender: male

Trade: Electrician

Re: 240 Volt Generator
Reply #21 - Oct 25th, 2004, 8:40am
 
Been away for a few days just catching up on gossip

JerryD one comment you made rang alarm bells

Wife & 2 daughters and you have a lead with 13a plug each end - chuck it away don't play russian roullette with your family.

We all take risks & you might be happy to risk your own life but don't risk your families.

Make your system idiot proof it shooldn't cost that much compared with a funeral

Sorry to seem a bit harsh but I used to work in Explosives and saw a close friend killed thru taking a calculated risk!!!

Cheers

Dave
Back to top
 

I've heard it all, I've seen it all, I've done it all&&I just don't remember any of it!
Thank User For This Post View members image gallery  
IP Logged
 
JerryD
Re: 240 Volt Generator
Reply #22 - Oct 25th, 2004, 5:50pm
 
I hear ya!!  Grin

You're all making me feel guilty now, guess I'll have to 'upgrade' my installation.

Thanks for your concern.  Smiley
Back to top
 
Thank User For This Post  
IP Logged
 
Pages: 1 
Send Topic Print