Quote:Checked today no neytarl in the box!! Typical.
Had a feeling
Quote:I've got to have the carpet up in the hall next week. While it's up could i run a single cable from the CU on its own MCB from the RCD side of the CU??
Not a single cable no, would be better to make a new box in the wall and run some new twin+earth to it from a new breaker, or alternatively run another twin cable down from an adjacent light fitting with a permanent live.
You must keep the same neutral that is associated with the live otherwise it's not safe and contradicts the regs.
In other words you can't take a neutral from another circuit on it's own, you must take a live and neutral from one existing circuit, or make another.