2 gang light switch (Read 14020 times)
Chaddy
GDPR opt-out









2 gang light switch
Dec 31st, 2004, 5:20pm
 
Hi guys

I want to fit an outside light. i currently have a 2 way switch fitted in the kitchen. I was going to drill through the wall and fit a 2 gang switch. Can i pick up a live from the current set up and link accross to the 1 way side of the switch?
If so which one??
Cheers and Happy New Year to everyone.  Grin Grin Grin Grin
Back to top
« Last Edit: Dec 31st, 2004, 5:20pm by Chaddy »  
 
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #1 - Dec 31st, 2004, 5:22pm
 
You will also need a neutral, and these are not always present in switches.

Take the plate of the wall, and tell us what cables are already behind the plate.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #2 - Dec 31st, 2004, 5:24pm
 
That was a quick reply!!!

There are red(fitted in the common), 2 x yellow and 2 x blue(which is a switched live i assume as it has a red marker on it. plus an earth.
Back to top
« Last Edit: Dec 31st, 2004, 5:38pm by Chaddy »  
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #3 - Dec 31st, 2004, 5:48pm
 
No extra terminal blocks in the back of the box with a blue or black Sad

Sounds like there is no neutral.

How many reds are there in the common?  No other red lurking or chopped off?

Sounds as if they may have used a 3 core to drop from the pendent, which could be in your favour, as the spare core could be used as a neutral.

Any chance of a photo??
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #4 - Dec 31st, 2004, 5:51pm
 
Only one red in the common.

No other wires!!
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #5 - Dec 31st, 2004, 5:55pm
 
Yellow and blue suggests that 3 core and earth cables have been used.

These cables have 1xred 1xyellow 1xblue core, plus an earth.

Are you sure there isn't another red lurking??
Back to top
« Last Edit: Dec 31st, 2004, 6:05pm by Lectrician »  

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #6 - Dec 31st, 2004, 5:58pm
 
I'll have to check and get back to you.

It's possible that i'm having a silly moment.

Cheers

Ken

Back to top
« Last Edit: Dec 31st, 2004, 9:23pm by LSpark »  
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #7 - Dec 31st, 2004, 9:23pm
 
Insult's to blonde people will not be tolerated here, sorry  Grin
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #8 - Dec 31st, 2004, 11:22pm
 
What about bald people???

Suddenly got very pc around here!! Grin
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #9 - Jan 1st, 2005, 1:36am
 
[quote author=Chaddy  link=1104513609/0#8 date=1104535374]Suddenly got very pc around here!! Grin [/quote]

lol, not really  8)
Back to top
« Last Edit: Jan 1st, 2005, 1:36am by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #10 - Jan 1st, 2005, 3:16pm
 
I'm glad about that!!!!

Theres too many do gooders in the world already!!! Tongue Tongue

Anyway the wires in the back of the switch are as follows....

Com- red
L1- yellow & red
L2-Blue & Blue with red marker
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #11 - Jan 1st, 2005, 3:35pm
 
Sorry I haven’t really followed this, You have a 2 gang switch of you have a 2-way switch?

Or it could be 2-gang & 2-way

2 gang's means 2 switches, 2-way means the light's can be controlled be either 2-way switch connected in parallel with each other.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #12 - Jan 1st, 2005, 4:27pm
 
I have a 2 gang switch. one switch is wired 2 way. The other i wanted to wire up 1 way to power the outside light! ??? Shocked
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #13 - Jan 1st, 2005, 5:20pm
 
What colours go into the individual cable sheaths??  The colours still sound a little odd.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #14 - Jan 1st, 2005, 5:48pm
 
Ok, so it's a 2 gang 2-way, with one 2-way and one 1-way.

It's probably fine lecc, but talking about it and seeing it are miles apart.

Quote:
Back to normality...


Whats that lecc?  Wink
Back to top
« Last Edit: Jan 1st, 2005, 5:48pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #15 - Jan 1st, 2005, 5:51pm
 
Its currently a 1gang 2way.

He wants to put a 2gang 2way in, the extra ang for an outside light.

He want to run the cable from switch directly to light.

We are trying to see if there is a neutral at the switch, or if we could put one there, as it looks like 3 core has been used for the switch drop as well as the strapper.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #16 - Jan 1st, 2005, 5:53pm
 
Well I would think it's unlikely theres a neutral there, however this is where it bugs me becasuse if he had a voltage indicator like we all do it would be found out in a few seconds if there's a neutral, but normal house goers just dont have these things   Roll Eyes
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #17 - Jan 1st, 2005, 5:56pm
 
first time in a long time i've been called normal!!!
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #18 - Jan 1st, 2005, 5:56pm
 
lol, sorry my mistake, I was generalising  Cheesy Cheesy Cheesy Cheesy Cheesy
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #19 - Jan 1st, 2005, 5:59pm
 
Thats ok.

My Mum thinks i'm special!!! ; Embarrassed

More like special needs Grin Grin Grin
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #20 - Jan 1st, 2005, 11:34pm
 
lol, we do it all here  Grin
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #21 - Jan 1st, 2005, 11:36pm
 
Thanks for that L Spark.

Bloody good job!! Grin Grin

Happy New Year to you mate
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #22 - Jan 2nd, 2005, 12:45am
 
lol, you too

hope you get those switches sorted or some heads will roll  Cheesy
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #23 - Jan 3rd, 2005, 7:18pm
 
Hi all.
Checked today no neytarl in the box!! Typical.

I've got to have the carpet up in the hall next week. While it's up could i run a single cable from the CU on its own MCB from the RCD side of the CU??

That way i would ahve a neutral!!

Is this feasible?? Shocked ???
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #24 - Jan 3rd, 2005, 7:25pm
 
Quote:
Checked today no neytarl in the box!! Typical.


Had a feeling

Quote:
I've got to have the carpet up in the hall next week. While it's up could i run a single cable from the CU on its own MCB from the RCD side of the CU??


Not a single cable no, would be better to make a new box in the wall and run some new twin+earth to it from a new breaker, or alternatively run another twin cable down from an adjacent light fitting with a permanent live.

You must keep the same neutral that is associated with the live otherwise it's not safe and contradicts the regs.

In other words you can't take a neutral from another circuit on it's own, you must take a live and neutral from one existing circuit, or make another.
Back to top
« Last Edit: Jan 3rd, 2005, 7:27pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #25 - Jan 3rd, 2005, 7:31pm
 
What cores did you finally settle on behind the switch then??

The colours didn't seem to marry-up with convention.


I would take another 2core from the original light to the switch, and from the switch to the outside light.  Two blacks together in a terminal block, one red in com and one in L1 on the new switch.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Chaddy
Re: 2 gang light switch
Reply #26 - Jan 3rd, 2005, 8:09pm
 
Sorry LS when i said single cable i meant a 'radial' circuit with t+e. I assume a 6amp mcb is correct?

Lec looks like 2 3 core and earth have been run!! The  earth in one being cut off.

Would've made that into the neutral that i required but the ceiling has been overboarded and the ceiling rose is below that!!!

Another job for the future!!
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #27 - Jan 3rd, 2005, 9:00pm
 
You shouldn't ever use the bare copper earth as anything other than earth, this is bare so that if there's any damage to the cable e.g. a nail get's put trough it then it shorts to earth, which is preferable than a short between live/phase and neutral.
Back to top
« Last Edit: Jan 4th, 2005, 11:50pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
ban-all-sheds
Re: 2 gang light switch
Reply #28 - Jan 4th, 2005, 11:27pm
 
[quote author=L.Spark  link=1104513609/15#16 date=1104602038]Well I would think it's unlikely theres a neutral there, however this is where it bugs me becasuse if he had a voltage indicator like we all do it would be found out in a few seconds if there's a neutral, but normal house goers just dont have these things   Roll Eyes [/quote]
More fool them.

IMHO, not buying a multimeter when you want to mess with your electrics is like not buying a hammer when you want to bang nails in.
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #29 - Jan 4th, 2005, 11:49pm
 
[quote author=ban-all-sheds  link=1104513609/15#28 date=1104881271]
More fool them.

IMHO, not buying a multimeter when you want to mess with your electrics is like not buying a hammer when you want to bang nails in.
[/quote]

Yes perhaps

Multi-meters are good but they have there limits, and seeing as you could make mistakes if you don't know how to use one, set it wrong and then find the cable's still live.
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 2 gang light switch
Reply #30 - Jan 5th, 2005, 12:05am
 
the biggest danger with using a multimeter to prove dead is taking a bad reference

ie say you decide to measure voltage phase-neutral to prove dead

you check with the meter and get a voltage

turn a switch off check again and get no voltage

touch one of the cores and get a shock because there was a switch in the neutral.

Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: 2 gang light switch
Reply #31 - Jan 5th, 2005, 7:29am
 
I always test as normal, then put a probe on the wall - you always get near full volts.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Pages: 1 
Send Topic Print