Main Fuse Rating
Apr 15th, 2005, 1:39pm
 
As I have said before, I don't do domestics regularly, so please forgive what are possibly stupid questions!
Having just rewired the kitchen etc. It occurred to me (eventually) to check the Company fuse size.
I was surprised to find it is 60A. I'm sure the last house we has (much more recently built) was 100A.
Is it possible to get the supply authority fuse upgraded? (I realise that incoming feeder cable size etc. will have a bearing on it) Will it costme a fortune? Undecided
Back to top
 
Thank User For This Post 22,CARRIAGE+DRIVE,+BIDDULPH View members image gallery  
IP Logged
 
squirrel
Trade Member
*****
Offline

d'oh
Posts: 801


Total Thanks: 1
For This Post: 0


Gender: male

Trade: Electrician

Re: Main Fuse Rating
Reply #1 - Apr 15th, 2005, 1:48pm
 
Wozzer

You've answered the question yourself:

The rating of the service fuse should be appropriate to feed cable size to give adequate protection for the REC cable against overload.

You need to find out whether the REC's cable is adequate, if not it could be costly for them to upgrade.

Have you looked at the current loading and applied diversity to see whether there will be a problem with the existing 60A supply?

Sq
Back to top
 

I've heard it all, I've seen it all, I've done it all&&I just don't remember any of it!
Thank User For This Post View members image gallery  
IP Logged
 
supersparky
Administrator
Trade Member
Author
*****
Offline


Posts: 6097


Total Thanks: 3
For This Post: 0


Gender: male

Trade: Electrician



Re: Main Fuse Rating
Reply #2 - Apr 15th, 2005, 2:01pm
 
to be honest wozzer, the company fuse hardly ever goes, 60 amp is usualy fine unless your in a mansion Grin

ive been to places with 9 odd kw showers and huge electric range cookers on a 40 amp service fuse, i wouldent want to be near it whilst either is on though  Grin an added bonus was the house dident need central heating  Tongue

the rec will usualy upgrade, hell, ive seen em put nails in fuse carriers, very naughty.

ss
Back to top
 
Thank User For This Post WWW  
IP Logged
 
wozzer
Junior Member
**
Offline

The Jurassic Spark
Posts: 59


Total Thanks: 0
For This Post: 0


Gender: male



Re: Main Fuse Rating
Reply #3 - Apr 15th, 2005, 2:03pm
 
I see what you mean about having answered the question, but how do I find out what the suppliers cable rating is? do I just phone ? - I've had precious little luck getting them interested in replacing the seal on the meter teminal chamber!
If I apply diversity, 60A does look ok, but if I know my wife, she'll want to use every ring on the hob (halogen actually) AND the fan oven at the same time. - Now 60A starts to look dodgy...
Back to top
 
Thank User For This Post 22,CARRIAGE+DRIVE,+BIDDULPH View members image gallery  
IP Logged
 
wozzer
Junior Member
**
Offline

The Jurassic Spark
Posts: 59


Total Thanks: 0
For This Post: 0


Gender: male



Re: Main Fuse Rating
Reply #4 - Apr 15th, 2005, 2:05pm
 
I was typing as you replied SS so I didn't see your answer staright away. Thanks for the info guys, I guess I'll just ring 'em and ask for a bigger fuse??
- Nails ? In fuse carriers ?
Nah, don't believe it Shocked
Actually, many years ago we used to call 'em "Clog Tips" when someone did that Tongue
When I was an apprentice, I recall a spark who used it as a fault-finding technique when faced with finding out which bulkhead fitting out of the three hundred or so in a factory basement was faulty. - Answer? the one that jumped off the ceiling! Grin
Seriously, it is not something that should be done! I'm sure everyone is aware, just wouldn't want anyone to think I condone the practice Wink
Back to top