3 spurs together (Read 2570 times)
supra59
GDPR opt-out









3 spurs together
Feb 12th, 2005, 10:01pm
 
hi lads can anyone see a problem with wiring three fused spurs together my problem is as follows. there is no spare ways in the board apart from 1, i have 3 internal aircon units to wire all drawing short of 5 amp each on startup ,so i plan to use 2.5 t&e with a 16amp mcb type c and five amp fuses in the 3 switched spurs.
i no i could fit a suplementory consumer unit but i dont see any probs in doing it the other way apart from if the 16 amp mcb trips all aircon units are going to go off but that the only down fall i see please give me your comments

            thanks in advance supra
Back to top
 
 
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: 3 spurs together
Reply #1 - Feb 13th, 2005, 12:15am
 
sounds ok but keep an eye on the earth fault loop if using C16 breakers with 2.5mm cable especially if your Ze is near the high end of the acceptable range and/or your run is long.





Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 3 spurs together
Reply #2 - Feb 13th, 2005, 2:00am
 
C16 with 2.5mm cable, you should have no problems, don't go too far with you're cable though  Roll Eyes
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
supra59
Re: 3 spurs together
Reply #3 - Feb 14th, 2005, 10:48pm
 
thanks again for your inputs just thought it was worth a mention before i did the job thanks again supra
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: 3 spurs together
Reply #4 - Feb 14th, 2005, 11:00pm
 
don't go getting shocks now, getting used to seeing you here  Grin
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Page Index Toggle Pages: 1
Send Topic Print