Welcome, Guest. Please Login or Register
Welcome To Ask The Trades!
May 21st, 2024, 10:50pm
Quote: Why is the alphabet in that order? Is it because of that song?


Pages: 1 2 
Send Topic Print
Smoke detectors (Read 21642 times)
JohnD
GDPR opt-out









Smoke detectors
Feb 26th, 2005, 7:37pm
 
Thought I'd about got there with my rewire and then someoe said 'Have you fitted the smoke detectors'.  Sniff!

I have three linked units to install.  

As far as I can see from the instructions I will need a dedicated feed from the CU, which isn't a problem.

Questions.

1. Is a 6amp MCB sufficient?

2. Do I put it on the RCD side or the non RCD side of the CU?

3. Is it o.k. to use 1.5mm cable?  And then 3 core and E to link between the detectors?

And then I think I really HAVE finished the rewire!!

Units are Garvan (Screwfix) SS-1238S with 9v battery backup  220 - 240v  55mA in operation.

Thanks

JohnD
Back to top
« Last Edit: Feb 26th, 2005, 7:39pm by tjohndavies »  
 
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #1 - Feb 26th, 2005, 9:47pm
 
[quote author=JohnD  link=1109446657/0#0 date=1109446657]Thought I'd about got there with my rewire and then someoe said 'Have you fitted the smoke detectors'.  Sniff! [/quote]
Such is life  Grin

Quote:
As far as I can see from the instructions I will need a dedicated feed from the CU, which isn't a problem.

Yep, give it it's own feed

Quote:
1. Is a 6amp MCB sufficient?

Yes

Quote:
2. Do I put it on the RCD side or the non RCD side of the CU?

Non RCD side

Quote:
3. Is it o.k. to use 1.5mm cable?  And then 3 core and E to link between the detectors?

Yes, 1.5mm 2core and earth for feed to first unit, 3core and earth for the connection between first and all others

Quote:
Units are Garvan (Screwfix) SS-1238S with 9v battery backup  220 - 240v  55mA in operation.

good good, as long as there BS/BS EN marked, certified etc
Back to top
« Last Edit: Feb 26th, 2005, 9:48pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
BigT
Trade Member
*****
Offline

sh*t Happens
Posts: 605


Total Thanks: 0
For This Post: 0



Trade: Electrician

Re: Smoke detectors
Reply #2 - Feb 27th, 2005, 1:59pm
 
is one of them a heat detector for the kitchen I hope.

T
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #3 - Feb 27th, 2005, 2:07pm
 
Detectors should be placed with in 3m of any habitable room I think - No need for a detector IN the kitchen Wink

1mm t+e, and 1mm 3core+e would be the best bet - 1.5 is noticeably larger to fit into these small devices!
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
BigT
Trade Member
*****
Offline

sh*t Happens
Posts: 605


Total Thanks: 0
For This Post: 0



Trade: Electrician

Re: Smoke detectors
Reply #4 - Feb 27th, 2005, 2:37pm
 
Better check your regulations mate a heat detector is required in a kitchen now

T
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #5 - Feb 27th, 2005, 2:41pm
 
Building regs? Since when?
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #6 - Feb 27th, 2005, 3:02pm
 
Who when how!, bloody reg changes 24/7  Wink
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
BigT
Trade Member
*****
Offline

sh*t Happens
Posts: 605


Total Thanks: 0
For This Post: 0



Trade: Electrician

Re: Smoke detectors
Reply #7 - Feb 27th, 2005, 5:12pm
 
As told you Heat detectors should be fitted in kitchen since 2000. look here on page 5

http://www.tlc-direct.co.uk/Technical/DataSheets/Kidde/Guide_To_RSA.pdf hope that sorts this out.

Regards T
Back to top
« Last Edit: Feb 27th, 2005, 5:14pm by BigT »  
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #8 - Feb 27th, 2005, 5:17pm
 
Yea, that has been around for ages.

This is when a kitchen is part of a room, in a bedsit for example.

If there is a firedoor between the kitchen and a habitable room(as in most new builds), this can be ignored.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
BigT
Trade Member
*****
Offline

sh*t Happens
Posts: 605


Total Thanks: 0
For This Post: 0



Trade: Electrician

Re: Smoke detectors
Reply #9 - Feb 27th, 2005, 5:28pm
 
Look at the drawings on page 2 bruv
Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #10 - Feb 27th, 2005, 6:23pm
 
I stick to what I say.  You are looking at a recommendation from a sales team.
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
JohnD
Re: Smoke detectors
Reply #11 - Feb 27th, 2005, 8:17pm
 
No, (sob Cry) one of them isn't a heat detector (sob Cry) I didn't know it had to be.....

Never mind, one of the smoke detectors will be close enough to run a feed from if Building Control think it is necessary.  Thanks for the advice so far.

JohnD
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #12 - Feb 27th, 2005, 8:43pm
 
lol it could be a mistake T, remember the dual earth terminal socket's in ALL homes?   Shocked
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
BigT
Trade Member
*****
Offline

sh*t Happens
Posts: 605


Total Thanks: 0
For This Post: 0



Trade: Electrician

Re: Smoke detectors
Reply #13 - Feb 28th, 2005, 5:33pm
 
Have you seen the recommended amount of sockets you should put in a house these days LS even one by a phone socket for recharging. Dont worry though LS you wont need that one though some bugger nicked yours lol sorry couldnt resist tuchay as they say Lol.

Regards T  Grin
Back to top
 
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #14 - Feb 28th, 2005, 10:04pm
 
Sad
Back to top
« Last Edit: Feb 28th, 2005, 10:05pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
CWatters
Super Member
*****
Offline

"Daddy fick it" says James

Posts: 5150


Total Thanks: 58
For This Post: 0


Gender: male

Re: Smoke detectors
Reply #15 - Mar 3rd, 2005, 10:32am
 
[quote author=Lectrician  link=1109446657/0#8 date=1109524660]If there is a firedoor between the kitchen and a habitable room(as in most new builds), this can be ignored. [/quote]

Does there _have_ to be a fire rated door between a kitchen and a living room these days? I was planning to fit a glass door but I suspect they aren't classed as fire doors...
http://www.flora-glasdesign.de/


Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8815


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Smoke detectors
Reply #16 - Mar 3rd, 2005, 4:42pm
 
How often do you see a door during the building control inspection.....and then it becomes an archway!

Ask your question again in the building section.  You may get a better answer  Wink
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Pages: 1 2 
Send Topic Print