Safety of light fittings (Read 8205 times)
akuk
GDPR opt-out









Safety of light fittings
Jun 22nd, 2005, 10:31pm
 
Hi, I have been asked to remove few light fittings from a house and install them in a new house, (just built).
I have my ideas but I would like to hear yours as well:
1) is it ok to leave the wires in the old house terminated with a connection block, instead of the removed light fittings?
2) After removing the light fittings do I need to test the circuits, or I can assume that under the regs. when a house changes hands a periodic inspection will be carried out any how + someone will put new lights and will have to test .
3) does the removal of lights require certificate? (Minor works)
3) The new house was just built,  does it come under changing owner or I can rely on the fact that it is new and was tested, and so test only the relevant circuits that I modified?.
Albert
Back to top
 
 
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #1 - Jun 23rd, 2005, 12:09am
 
Firstly, don't rely on anything albert, ever

Quote:
1) is it ok to leave the wires in the old house terminated with a connection block

No, all connection's must be enclosed, so you would need to have a junction box or a chocbox even better, you can get these from a wholesaler or screwfix

Quote:
2) After removing the light fittings do I need to test the circuits, or I can assume that under the regs. when a house changes hands a periodic inspection will be carried out any how + someone will put new lights and will have to test .

Theres no need to test if you're removing fittings, just make safe all connections, anything done after you leave is down to the person ordering or doing the work

Quote:
3) does the removal of lights require certificate? (Minor works)

Not that I'm aware of
Quote:
3) The new house was just built,  does it come under changing owner or I can rely on the fact that it is new and was tested, and so test only the relevant circuits that I modified?.

Not exactly sure what you mean by this question. If it's a like for like swap there's no requirement to test, however regulations state that equipotential bonding must be checked before any work is carried out., and again you can't assume or rely on anything when carrying out work.
Back to top
« Last Edit: Jun 24th, 2005, 11:20pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
akuk
Re: Safety of light fittings
Reply #2 - Jun 23rd, 2005, 6:41am
 
[quote author=L.Spark  link=1119475889/0#1 date=1119481791]Firstly, don't rely on anything albert,ever [/quote]
Yep, I never do, that is why you hear from me all the time.
Quote:
Not exactly sure what you mean by this question. If it's a like for like swap there's no requirement to test, however regulations state that equipotential bonding must be checked before any work is carried out., and again you can't assume or rely on anything when carrying out work.

I mean that, if someone buys a house from another person and both houses are old (people lived in before), the regs. are very cleare that a periodic inspection has to be carried out, my question relats to a completely new house that was just built and these people will be the first to live in, theoretecally the constructor should provide them all the certs. necessary, do I need to test again? or just do the work and certify the relevant circuits.
Back to top
 
Thank User For This Post  
IP Logged
 
santacruz
Re: Safety of light fittings
Reply #3 - Jun 23rd, 2005, 6:56am
 
I think you will find the to-be buyers solicitor will be up in arms if you simply leave choc blocks at light fittings.

Why not simply shove up some pendants - I purchased a box of ten recently £1 each!! Yes they were new, no they were not stolen, they were acquired from a very large outlet. Cheaper than a chocbox!

Back to top
 
Thank User For This Post  
IP Logged
 
Lectrician
Administrator
Trade Member
Author
*****
Offline

Ask The Trades
Posts: 8814


Total Thanks: 109
For This Post: 0


Braunton, North Devon, United Kingdom
Braunton, North Devon
United Kingdom

Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #4 - Jun 23rd, 2005, 4:19pm
 
Yep, you need to put up roses.

Umm....certs, as it is not replacing like for like, it is not maintenance and requires a cert (minor works) Angry

So strictly speaking, if no main bonding.......
Back to top
 

Need to post a picture? Click HERE for info!
Thank User For This Post WWW View members image gallery  
IP Logged
 
Beanzy
Re: Safety of light fittings
Reply #5 - Jun 23rd, 2005, 8:26pm
 
Yep, nowt to do with our regs, but plenty to do with the sale of the house. If they want the old fittings they have to leave the house with the same number of light fittings in the same place as when the purchaser viewed and agreed the purchase. Normally just swap for pendant (maintenance) and do a M/W cert with the loop and what not.

If they leave nothing they could be stung badly by a suit.
Back to top
 
Thank User For This Post  
IP Logged
 
plugwash
Administrator
*****
Offline

I love YaBB 1G - SP1!

Posts: 1383


Total Thanks: 0
For This Post: 0



Trade: Not Specified

Re: Safety of light fittings
Reply #6 - Jun 23rd, 2005, 11:42pm
 
surely changing the light fittings for a less desirable type between viewing and sale could cause issues with the buyers
Back to top
 
Thank User For This Post WWW plugwash plugwash 107767391 peter_m_green_zyworld_com plugwash  
IP Logged
 
Lurch
Re: Safety of light fittings
Reply #7 - Jun 24th, 2005, 12:32am
 
[quote author=plugwash  link=1119475889/0#6 date=1119566526]surely changing the light fittings for a less desirable type between viewing and sale could cause issues with the buyers [/quote]
Depends what's listed in the fixtures & fittings list and what agreement was made between them. It's not our problem anyway, it's between the seller and buyer.
Back to top
 
Thank User For This Post  
IP Logged
 
JerryD
Re: Safety of light fittings
Reply #8 - Jun 25th, 2005, 8:06am
 
[quote author=plugwash  link=1119475889/0#6 date=1119566526]surely changing the light fittings for a less desirable type between viewing and sale could cause issues with the buyers [/quote]

This is true, might as well change all the internal walnut veneer doors for B&Q hardboard doors while you're there  Undecided

I'd get the order to remove these fitings in writing so that you don't get any of the flack if there is a dispute with the buyer of the house who may be expecting the nice light fittings to still be there when they move in.

There have been many court cases over situations like this, one family moved in only to find all the patio paving had been removed!  Shocked
Back to top
« Last Edit: Jun 25th, 2005, 8:06am by JerryD »  
Thank User For This Post  
IP Logged
 
akuk
Re: Safety of light fittings
Reply #9 - Jun 25th, 2005, 10:51am
 
Hi, I am pleased to see that I made you all busy again... Wink
1) this is an exchange, the builder buys the old house from my customer and sales her a new house. So you can see it can be a lots of negotiations here.
Quote:
Posted by: santacruz Why not simply shove up some pendants - I purchased a box of ten recently £1 each!! Yes they were new, no they were not stolen, they were acquired from a very large outlet. Cheaper than a chocbox!

I am holding in my hands Pendents and few jB's that I got just in case, and I paid about what you said under £10 for 4 pendents and 4 20A JBs.
Quote:
Posted by: Lectrician Posted on: Jun 23rd, 2005, 4:19pm
Yep, you need to put up roses.
Umm....certs, as it is not replacing like for like, it is not maintenance and requires a cert (minor works)  
So strictly speaking, if no main bonding.......  

I think that I need a hint on this one...can you explain?  The minor work, cert. as you know, is not the issue, I don't want to spend to much time there when it is not necessary but I want to do the right thing...as well as I would like to give a realistic quote.
Quote:
Posted by: JerryD Posted on: Today at 8:06am on Jun 23rd, 2005, 11:42pm,  
I'd get the order to remove these fitings in writing...

This is something I learnt from working as a service engineer (30 years), every job order has to be written, and this one no different.
I am not worried about the legal issue, as I am doing what asked to do (in writing), please can you experts agree what would be the proper and reasonable way to do this Grin?, Installing the fitting in the new house is more simple, as it is brand new, I adviced the customer to make sure that the builder will provide her with all the documentations, and certificats, when I concetrated on the electrics, I mentione the Electrical installation cert., scdhedule of inspection and schedule of test resaults.
Back to top
« Last Edit: Jun 25th, 2005, 11:00am by akuk »  
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #10 - Jun 25th, 2005, 10:51pm
 
Quote:
Hi, I am pleased to see that I made you all busy again

Are you stirring it all up again Albert  Grin
Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
akuk
Re: Safety of light fittings
Reply #11 - Jun 26th, 2005, 10:59am
 
[quote author=L.Spark  link=1119475889/0#10 date=1119736291]
Are you stirring it all up again Albert  Grin [/quote]
No, I trying to make it clear... Angry
I promise that if you find a clear answer to this one, I will let you go... 8) (don't be so happy, only on this issue.. Wink)
My question is; after changing the light fittings with the standard pendent fittings (in the house that was sold), do I need to test the relevant circuits? I think that it is changing like with like, (I will provide a Minor works any how..).  I went to see the house and it seems that they have no problem with the main bonding, the system is TN-S, and there is a connection between the main earth terminal and the gas & water pipes, BTW- is this enough to calim that  there is an indirect protection by EEBADS? (this is as a response to Lectrician's remark...)
Back to top
« Last Edit: Jun 26th, 2005, 11:05am by akuk »  
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #12 - Jun 26th, 2005, 12:44pm
 
Quote:
My question is; after changing the light fittings with the standard pendent fittings (in the house that was sold), do I need to test the relevant circuits?

If you end up doing a Minor work's as it's not like for like replacement, then you're be testing that particular circuit anyway
Back to top
« Last Edit: Jun 26th, 2005, 12:48pm by LSpark »  
Thank User For This Post View members image gallery  
IP Logged
 
Beanzy
Re: Safety of light fittings
Reply #13 - Jun 27th, 2005, 1:43am
 
The rating of the pendants doesn't change? they're still Class1? then it's maintainance, not a new load point, change of class, or increased load, so MW will be the correct cert. You could however just test and record and file, as it's not strictly an alteration to the circuit. Can be handy if you just want to list a stack of similar swap-outs ie: same info as MW but just all on one letter/cert.

If there's a fault such as main bonding you shouldn't alter anything until that's sorted anyway. So if they want to shift their fittings they need to do so leaving the installation safe. (ie need would to get the bonding sorted)
Back to top
 
Thank User For This Post  
IP Logged
 
akuk
Re: Safety of light fittings
Reply #14 - Jun 27th, 2005, 8:22am
 
[quote author=Beanzy  link=1119475889/0#13 date=1119833004]The rating of the pendants doesn't change? they're still Class1? then it's maintainance, not a new load point, change of class, or increased load, so MW will be the correct cert. You could however just test and record and file, as it's not strictly an alteration to the circuit. Can be handy if you just want to list a stack of similar swap-outs ie: same info as MW but just all on one letter/cert. [/quote]
It sounds right, just changing to standard fittings, with standard bulbs, no change on: position, load or any other part.

Quote:
If there's a fault such as main bonding you shouldn't alter anything until that's sorted anyway. So if they want to shift their fittings they need to do so leaving the installation safe. (ie need would to get the bonding sorted)

the system is TN-S, and there is a connection between the main earth terminal and the gas & water pipes, BTW- is this enough to calim that  there is an indirect protection by EEBADS? and bonding exists, or there is another way or requirements?

Back to top
 
Thank User For This Post  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #15 - Jun 27th, 2005, 1:44pm
 
To be honest, I'd just get on and change the fittings.

This is becoming far too complicated for its own good.

Firstly, its just a swap, so there's no real need for any paperwork apart from your invoice.

You haven't carried out work on other parts of the electrical installation, and if its a new build, the original contractor will have certed it all.
(Hope I'm correct here - same house as the one in your other thread?)

Bonding shouldn't be an issue if the place is new.
By all means check to see if there a 2 x 10mm cables in the CU, along with the 16mm main earthing conductor - that's as far as I'd go with it.

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Safety of light fittings
Reply #16 - Jun 27th, 2005, 1:50pm
 
One other thing - If the light fittings you are removing from the 'old house' are all metal or require an earth(class 1), and there isn't a cpc at each fitting, then you are actually doing the right thing by removng these unearthed fittings!
I presume the 'new house' will already have a cpc at each lighting point, so you're ok there.

I'd say YES - you can claim EEBADS is alive and well at both properties.

TT