Rings (Read 2494 times)
molerat
GDPR opt-out









Rings
Nov 30th, 2004, 11:04pm
 
I have a large cupboard that backs onto my kitchen.  This cupboard has a socket in it which is on the downstairs ring.  I am going to enlarge my kitchen by removing the stud wall between the kitchen and this cupboard and blocking off its doorway.  This will bring the socket into the kitchen area which has its own ring.  How does this stand regulation (and common sense) wise ? ???
Back to top
 
 
IP Logged
 
The_Trician
Trade Member
*****
Offline


Posts: 7721


Total Thanks: 8
For This Post: 0


Gender: male

Trade: Electrician



Re: Rings
Reply #1 - Nov 30th, 2004, 11:25pm
 
Regswise there's no issue at all. Commonsense-wise its difficult to tell without seeing the job.

I assume you already have sockets in your kitchen? If so, its a good idea for the cupboard socket to be on the same circuit as the kitchen sockets so that if you switch the mcb off or pull the Ring fuse, you'll know that ALL of the sockets are dead in the kitchen.

Now that's common sense!

Wink Wink Wink

TT
Back to top
 

Thats the trouble with a colostomy - you can never find the shoes to match the bag.......
Thank User For This Post  
IP Logged
 
LSpark
Global Moderator
Trade Member
Author
*****
Offline


Posts: 8069


Total Thanks: 3
For This Post: 0


London, UK, United Kingdom
London, UK
United Kingdom

Gender: male

Trade: Electrician



Re: Rings
Reply #2 - Nov 30th, 2004, 11:26pm
 
[quote author=molerat  link=1101855872/0#0 date=1101855872]I have a large cupboard that backs onto my kitchen.  This cupboard has a socket in it which is on the downstairs ring.  I am going to enlarge my kitchen by removing the stud wall between the kitchen and this cupboard and blocking off its doorway.  This will bring the socket into the kitchen area which has its own ring.  How does this stand regulation (and common sense) wise ? ??? [/quote]

Well firstly it depends upon where the socket is located, e.g. away from sources of water and excess heat

Secondly all sockets that can 'reasonably' supply portable equipment outside should be RCD protected, this could be either an RCD Socket or an RCD unit protecting the ring circuit located in the consumer unit




Back to top
 
Thank User For This Post View members image gallery  
IP Logged
 
Stoday
Re: Rings
Reply #3 - Dec 1st, 2004, 12:19am
 
[quote author=The_Trician  link=1101855872/0#1 date=1101857134]

Now that's common sense!

[/quote]

Common sense is to test & prove it's dead, not to assume you know which fuse or mcb protects it.

Back to top
 
Thank User For This Post  
IP Logged
 
big-e
Junior Member
**
Offline

The (piss)artist formerly
known as Mice!
Posts: 55


Total Thanks: 0
For This Post: 0


Gender: male

Re: Rings
Reply #4 - Dec 1st, 2004, 1:20am
 
I'd say its good practice rather than common sense Wink  My new house has 16 mcb's and not one of them is labelled Angry